1. Interstitial Duct Colored Insulation System

  • l Use flame-retardant PIR/PUR foam insulation with density ≥48kg/m³ and thermal conductivity ≤0.022W/(m·K)
  • l Insulation thickness designed per process requirements, typically 25-40mm, with colored PVC protective layer
  • l Ensure specialized tape sealing at joints with smooth, wrinkle-free surface
latest company case about Ventilation Ductwork System for Biopharmaceutical Cleanrooms  0

2. Return Air Riser Installation

  • l Use 304 stainless steel rectangular ducts with wall thickness ≥1.2mm
  • l Vertical deviation ≤2mm/m, total length deviation ≤10mm
  • l Support spacing ≤3m with rubber vibration isolators
latest company case about Ventilation Ductwork System for Biopharmaceutical Cleanrooms  1

3. High-Efficiency Air Outlet Edge Banding

  • l Use anodized aluminum trim with thickness ≥2mm
  • l Apply medical-grade silicone sealant at joints, 3-5mm bead width
  • l Install EPDM gasket at color steel panel connections
latest company case about Ventilation Ductwork System for Biopharmaceutical Cleanrooms  2

4. Stainless Steel Air Outlet Installation Standards

  • l Select 316L medical-grade stainless steel with electropolished surface
  • l Pre-installation laser leveling with deviation ≤1.5mm/m
  • l Use quick-release flange connections at duct joints
latest company case about Ventilation Ductwork System for Biopharmaceutical Cleanrooms  3

5. Duct Wall Penetration Sealing System

  • l Provide sleeves 50mm larger than duct diameter, filled with fireproof rockwool
  • l Seal both sides with fire-resistant putty, thickness ≥30mm
  • l Install stainless steel finishing rings
latest company case about Ventilation Ductwork System for Biopharmaceutical Cleanrooms  4

6. Exhaust Fan Grounding Specifications

  • l Use 6mm² yellow-green copper wire for grounding
  • l Apply OT terminal crimping with anti-loosening washers
  • l Quarterly grounding resistance testing with documented records
latest company case about Ventilation Ductwork System for Biopharmaceutical Cleanrooms  5

7. Integrated Ceiling BIM Coordination

  • l Conduct clash detection using Revit+Navisworks
  • l Maintain ≥600mm access clearance with ≥300mm equipment spacing
  • l Provide 3D isometric drawings for construction guidance
latest company case about Ventilation Ductwork System for Biopharmaceutical Cleanrooms  6

8. Crossover Walkway Technical Requirements

  • l Main structure using hot-dip galvanized steel with ≥85μm zinc coating
  • l Tread plates made of 304 stainless steel grating with ≤20mm openings
  • l Install double-rail guardrails with intermediate wire rope protection
latest company case about Ventilation Ductwork System for Biopharmaceutical Cleanrooms  7

9. Supplementary Technical Specifications

  • l All ducts require PAO leak testing
  • l System noise control at ≤65dB(A)
  • l Final air balance report required upon completion